- Date
- 10/05/2018
- W/O
- 0731552
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00763
- PipeID
- P25689
- Time
- 12:46 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0996
- Sewer Name
- 21 DISTRICT #21 OUTFALL TRUNK
- City
- INDUSTRY
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 21
- Page No.
- 28
- Purpose
- Maintenance Related
- Project
- 20181005MDM_DISTRICT_21_OUTFALL_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 27 in.
- Upstream MH
- 21 1298
- Downstream MH
- 21 1297
- Dir. of Survey
- Downstream
- Length Surveyed
- 170.6 ft.
- Total Length
- 170.6 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 2
Pipe schematic from manhole 21 1298 to 21 1297 Observation photos (8)

8.8 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: YES - CORRISION AT JOINT

70.4 ft. - General Observation - WHITE COATING ON PIPE 8:00 TO 4:00

70.9 ft. - General Observation - WHITE COATING

92.6 ft. - General Observation - WHITE COATING

104.8 ft. - General Observation - WHITE COATING

105.9 ft. - General Observation - WHITE COATING

132.9 ft. - General Observation - WHITE COATING

170.6 ft. - Survey Abandoned - 2:20AM