Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2015, 10:14 AM
  • 02 2241_02 2240_20150910_022824.mp4

Date
09/10/2015
W/O
525344
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00253
PipeID
P04515
Time
3:14 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2741
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION RELIEF TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_525344_TV02332_SEPT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 2241
Downstream MH
02 2240
Dir. of Survey
Downstream
Length Surveyed
391.6 ft.
Total Length
391.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 2241 to 02 2240
MH: 02 2241MH: 02 2240downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 22410 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH18.6 ft. LR - Alignment Right, 10 %301.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO358 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start390.2 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Finish391.6 ft. AMH - Downstream Manhole, Survey Ends - 02 2240

Observations (9)

DistanceCodeObservation
0MWL
390.2DSZ
0MWM
301.5DSZ
358DSZ
0AMH02 2241
391.6AMH02 2240
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
18.6LR

Properties (4)

custom_field_two
4
customer
LACSD
datetime
2015-09-10T03:14:39-07:00
year_laid
19860128