Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 22, 2016, 10:41 AM
  • 02 1785_02 1784A _20160722_034157.mp4

Date
07/22/2016
W/O
582912
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00275
PipeID
P04136
Time
3:41 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3620
Sewer Name
02 INDIANA STREET RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
07A
Purpose
Routine Assessment
Project
WO_582912_TV02067_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1784A
Downstream MH
02 1785
Dir. of Survey
Upstream
Length Surveyed
197.3 ft.
Total Length
197.3 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2O00
O&M Rating
156
Overall Index
2
Overall Quick
Overall Rating
158
Pipe schematic from manhole 02 1784A to 02 1785
MH: 02 1784AMH: 02 1785upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 17850 ft. MGO - General Observation - COCKROACHES IN MANHOLE1.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish133 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES148.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start195.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start197.3 ft. AMH - Downstream Manhole, Survey Begins - 02 1784A197.3 ft. MWM - Water Mark, 20 %of cross sectional area197.3 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (4)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    64.3 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    197.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
197.3AMH02 1785
197.3MGOCOCKROACHES IN MANHOLE
2DAE
0AMH02 1784A
0MWM
195.4DAE
48.5TFC
195.4DAGS
0MWL
64.3CS
2DAGS

Properties (4)

additional_info
SC305799
custom_field_two
4
customer
LACSD
datetime
2016-07-22T03:41:34-07:00