Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2016, 08:47 AM
  • 05 1890_05 1889 _08082016_014841.mp4

Date
08/08/2016
W/O
579954
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00491
PipeID
P07117
Time
1:47 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3628
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 2
City
ROLLING HILLS ESTATES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
40
Purpose
Routine Assessment
Project
WO_579954_TV05079_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
05 1890
Downstream MH
05 1889
Dir. of Survey
Downstream
Length Surveyed
484.2 ft.
Total Length
484.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
3124
O&M Rating
13
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole 05 1890 to 05 1889
MH: 05 1890MH: 05 1889downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 18900 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 6 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start58.4 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"94.1 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"137.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"201 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"233.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"292.7 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"336.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS336.2 ft. RML - Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES367.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR369.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"375 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR421.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"422.6 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES428.7 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS456.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"484.2 ft. AMH - Downstream Manhole, Survey Ends - 05 1889484.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    336.1 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES

    336.2 ft. - Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR

    367.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR

    375 ft. - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    422.6 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    428.7 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

Observations (22)

DistanceCodeObservation
336.1TFDROOTS
0AMH05 1890
422.6CM
137.2TFA
484.2AMH05 1889
367.8RFJ
421.4TFA
94.1TBA
58.4TFA
0MWM
0MGOACTIVE CONNECTION AT MH 6 O'CLOCK
201TFA
375RFJ
292.7TFA
233.7TFA
456.9TFA
0MWL
484.2DAGS
428.7TFDROOTS
336.2RML
369.1TFA
2DAGS

Properties (4)

additional_info
SC306062
custom_field_two
4
customer
LACSD
datetime
2016-08-08T01:47:26-07:00