Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2016, 09:33 AM
  • 15 0986_15 0985_29032016_023357.mp4

Date
03/29/2016
W/O
563410
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00636
PipeID
P12761
Time
2:33 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3299
Sewer Name
15 VALINDA TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_563410_TV15038_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
15 0986
Downstream MH
15 0985
Dir. of Survey
Downstream
Length Surveyed
328.7 ft.
Total Length
328.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
135
Pipe schematic from manhole 15 0986 to 15 0985
MH: 15 0986MH: 15 0985downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 09860 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"75.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"98.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"174.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"187.6 ft. FS - Fracture Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES225.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"273.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"320.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"322.5 ft. CS - Crack Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES326.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK328.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0985328.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES

    187.6 ft. - Fracture Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES

    322.5 ft. - Crack Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    328.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
98.3TFC
187.6FS
328.7MGOACTIVE CONNECTION AT MH 9 O'CLOCK
273.5TFC
2DAGS
0MWM
328.7AMH15 0985
322.5CS
326.4DAGS
225.8TFC
320.9TFC
0AMH15 0986
0MGOCOCKROACHES IN MANHOLE
75.4TFC
174.3TBA
328.7MGOCOCKROACHES IN MANHOLE
0MWL
27.9TFC

Properties (4)

additional_info
SC305425
custom_field_two
3
customer
LACSD
datetime