- Date
- 12/15/2015
- W/O
- 521098
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00238
- PipeID
- P03790
- Time
- 2:18 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K2850
- Sewer Name
- 02 BELVEDERE TRUNK
- City
- LOS ANGELES
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 12
- Purpose
- Routine Assessment
- Project
- WO_521098_TV02329_AUG2015
- Sewer Type
- GRAVITY
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 02 1276
- Downstream MH
- 02 1275A
- Dir. of Survey
- Downstream
- Length Surveyed
- 199.5 ft.
- Total Length
- 199.5 ft.
- Structural Index
- 3
- Structural Quick
- 3B22
- Structural Rating
- 55
- O&M Index
- 2
- O&M Quick
- 2G00
- O&M Rating
- 78
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 133
Pipe schematic from manhole 02 1276 to 02 1275A Observation photos (3)

87.1 ft. - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

97.1 ft. - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

154.9 ft. - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES