Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2015, 07:54 AM
  • 02 1302_02 1301B_30102015_005550.mp4

Date
10/30/2015
W/O
521098
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00238
PipeID
P03821
Time
12:54 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2819
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_521098_TV02329_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1302
Downstream MH
02 1301B
Dir. of Survey
Downstream
Length Surveyed
142.3 ft.
Total Length
142.3 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
75
O&M Index
2
O&M Quick
2E00
O&M Rating
56
Overall Index
2
Overall Quick
Overall Rating
131
Pipe schematic from manhole 02 1302 to 02 1301B
MH: 02 1302MH: 02 1301Bdownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 13020 ft. MGO - General Observation - ROACHES IN MH0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 25 %of cross sectional area10.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"16.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"87.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"89.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"94.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.1 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"140.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish140.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish140.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE142.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1301B

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
125.1TF
142.3AMH02 1301B
10.2TF
16.2CM
140.7DAGS
94.6TF
0MWL
140.2TFC
87.6TB
140.7CM
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH02 1302
137.1TB
0MGOROACHES IN MH
140.7MGOCOCKROACHES IN MANHOLE
0DAGS
53.4TFA
89.3TFC
0MWM

Properties (4)

additional_info
SC204151
custom_field_two
3
customer
LACSD
datetime
2015-10-30T00:54:59-07:00