Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2015, 11:15 AM
  • 02 1313_02 1312_29102015_041620.mp4

Date
10/29/2015
W/O
521098
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00238
PipeID
P03833
Time
4:15 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2818
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_521098_TV02329_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1313
Downstream MH
02 1312
Dir. of Survey
Downstream
Length Surveyed
320.5 ft.
Total Length
320.5 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
187
Pipe schematic from manhole 02 1313 to 02 1312
MH: 02 1313MH: 02 1312downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 02 13130 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start9.4 ft. DAR - Deposits Attached Ragging, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES16.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"22.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"25.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start70.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"108.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"169.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"191 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"213.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"280.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"297.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"308 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"315.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish318.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish318.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish320.5 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK320.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1312320.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (2)

  • Deposits Attached Ragging, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    9.4 ft. - Deposits Attached Ragging, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    25.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (34)

DistanceCodeObservation
320.5MGOCAPPED CONNECTION AT MH 3 O'CLOCK
0MWM
2DAGS
75.3TFC
0MGOCOCKROACHES IN MANHOLE
320.5AMH02 1312
0AMH02 1313
106.3TFC
318.2CM
280.1TF
108.2TBA
25.2CM
195.4TBA
9.4DAR
119.1TFA
22.2TBA
16.3TFC
0MWL
191TFC
172.6TFC
167.3TFC
169.8TBA
297.6TFA
72.2TBA
177.5TBA
315.7TFC
308TBA
320.5MGOCOCKROACHES IN MANHOLE
318.2DAE
70.2TFC
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
318.2DAGS
2DAE
213.2TFA

Properties (4)

additional_info
SC204150
custom_field_two
3
customer
LACSD
datetime
2015-10-29T04:15:47-07:00