Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2016, 06:30 AM
  • 18 0763A_18 0763_20160502_235201.mp4

Date
04/26/2016
W/O
568699
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14621
Time
11:30 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3359
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_568699_TV18103_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
18 0763A
Downstream MH
18 0763
Dir. of Survey
Downstream
Length Surveyed
380.3 ft.
Total Length
380.3 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 0763A to 18 0763
MH: 18 0763AMH: 18 0763downstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 0763A7.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start34.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start94.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"151.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"166 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"373.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish375 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish379.3 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK380.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0763

Observation photos (2)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    34.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
375SAP
373.6SSS
0MGOLATERAL AT MH 9 OCLOCK
7.9SSS
380.3AMH18 0763
379.3MGOLATERAL AT MH 3 OCLOCK
0MWM
34.7SAP
166TF
0MWL
0AMH18 0763A
94.3TF
151.7TF

Properties (4)

additional_info
SC300356
custom_field_two
3
customer
LACSD
datetime