Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2017, 08:02 AM
  • 02 1405_02 1404_01062017_022551.mpg

Date
06/01/2017
W/O
635640
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02976
Time
1:02 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4612
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
WO_635640_TV02220_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
02 1405
Downstream MH
02 1404
Dir. of Survey
Downstream
Length Surveyed
300.2 ft.
Total Length
300.2 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 1405 to 02 1404
MH: 02 1405MH: 02 1404downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14050 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start257.2 ft. SRP - Surface Reinforcement Projecting, from 12 to 03 o'clock, within 8 inches of joint: YES299.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish300.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish300.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1404

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, from 12 to 03 o'clock, within 8 inches of joint: YES

    257.2 ft. - Surface Reinforcement Projecting, from 12 to 03 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
257.2SRP
0AMH02 1405
0MWL
299.8SAP
0MWM
2.3SAP
2.3SRV
300.2SRV
300.2AMH02 1404

Properties (4)

additional_info
SC345324
custom_field_two
2
customer
LACSD
datetime
2017-06-01T01:02:04-07:00