Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2017, 10:52 AM
  • 02 0882_02 0881_17072017_035320.mp4

Date
07/17/2017
W/O
646918
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00249
PipeID
P03449
Time
3:52 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4651
Sewer Name
02 DOWNEY TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_646918_TV02306_JUL2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0882
Downstream MH
02 0881
Dir. of Survey
Downstream
Length Surveyed
296.2 ft.
Total Length
296.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 0882 to 02 0881
MH: 02 0882MH: 02 0881downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 08820 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.9 ft. MGO - General Observation - MAG COAT49 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.3 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 2"150.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"254.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"296.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0881296.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

    136.3 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

Observations (16)

DistanceCodeObservation
158.4TF
296.2AMH02 0881
150.4TFC
160.2TF
0AMH02 0882
254.3TF
136.3TBI
49TFA
2.9MGOMAG COAT
0MWL
2.8SAV
156.3TF
189.9TFC
0MGOCONNECTION AT MH 3 O'CLOCK
296.2SAV
0MWM

Properties (4)

additional_info
SC345511
custom_field_two
3
customer
LACSD
datetime
2017-07-17T03:52:51-07:00