Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2018, 05:35 PM
  • Section#1_H 0404_H 0403A__1032018__I0079.mp4

Date
10/03/2018
W/O
0729413
Weather
Light Rain
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00177
PipeID
P10835
Time
10:35 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0079
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
WHITTIER
Loc. details
Yard
Location Code
Y
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
20181003SHO_JOINT_OUTFALL_H_UNIT_5A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
H 0404
Downstream MH
H 0403A
Dir. of Survey
Downstream
Length Surveyed
688.3 ft.
Total Length
688.3 ft.
Structural Index
3
Structural Quick
5C3L
Structural Rating
390
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
390
Pipe schematic from manhole H 0404 to H 0403A
MH: H 0404MH: H 0403Adownstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 04040 ft. MWM - Water Mark, 40 %of cross sectional area8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start106.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish325.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish443.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start688.3 ft. AMH - Downstream Manhole, Survey Ends - H 403A688.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    443.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
106.5SRC
0MWL
0AMHH 0404
325.7SAP
8SAP
688.3AMHH 403A
443.2SSS
688.3SSS
8SRC
0MWM

Properties (4)

custom_field_three
REBAR IS AGGREGATE IS VISIBLE
custom_field_two
2
customer
LACSD
datetime
2018-10-03T10:35:02-07:00