Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 22, 2017, 11:37 AM
  • 08 0082_08 0081 _22122017_034535.mp4

Date
12/22/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00110
Time
3:37 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5291
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
08 0082
Downstream MH
08 0081
Dir. of Survey
Downstream
Length Surveyed
168.9 ft.
Total Length
168.9 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
87
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
87
Pipe schematic from manhole 08 0082 to 08 0081
MH: 08 0082MH: 08 0081downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00820 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK16.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"21.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.1 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6" - POSSIBLE BREAK-IN65.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"118 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish168.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0081168.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
21.7CM
167.2CM
0MWL
16.9TFC
168.9AMH08 0081
118TF
168.9MGOCONNECTION AT MH 3 O'CLOCK
0MWM
0AMH08 0082
65.9TFC
0MGOCONNECTION AT MH 3 O'CLOCK
33.1TSPOSSIBLE BREAK-IN

Properties (4)

additional_info
SC346769
custom_field_two
3
customer
LACSD
datetime
2017-12-22T03:37:45-08:00