Wastewater/Activity/PacpInspection/1.0Dec 28, 2017, 11:29 AM
  • 08 0047_08 0046 _28122017_034128.mp4

Date
12/28/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00049
Time
3:29 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5297
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0047
Downstream MH
08 0046
Dir. of Survey
Downstream
Length Surveyed
307.2 ft.
Total Length
307.2 ft.
Structural Index
3
Structural Quick
3E22
Structural Rating
88
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
88
Pipe schematic from manhole 08 0047 to 08 0046
MH: 08 0047MH: 08 0046downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00470 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"55 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES62.1 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES87.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"98 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.1 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES111.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES132.8 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES147.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"196.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"246.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.8 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES297.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"305 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish306 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK307.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0046

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    55 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    62.1 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    100.1 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    111.8 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    132.8 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    283.8 ft. - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
87.5TFA
246.9TFC
47.5TF
100.1CM
111.8CL
0AMH08 0047
2CM
305CM
306MGOSPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK
132.8CM
98TF
196.3TF
147.4TFC
307.2AMH08 0046
0MWL
297.5TFC
283.8CM
0MWM
62.1CM
55CL