Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2017, 06:57 AM
  • 08 0063_08 0062 _27122017_231022.mp4

Date
12/27/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00065
Time
10:57 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5297
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0063
Downstream MH
08 0062
Dir. of Survey
Downstream
Length Surveyed
297.8 ft.
Total Length
297.8 ft.
Structural Index
3
Structural Quick
423C
Structural Rating
62
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
63
Pipe schematic from manhole 08 0063 to 08 0062
MH: 08 0063MH: 08 0062downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00630 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish11.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start71.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126 ft. RFJ - Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YES128.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"217 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start217 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish234.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"286.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"296 ft. MGO - General Observation - ENCRUSTRATION/SPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK297.8 ft. AMH - Downstream Manhole, Survey Ends - 08 0062297.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YES

    126 ft. - Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    217 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
0MWM
2.5CM
234.5TFC
286.3TFC
128.6TF
0MWL
71.2TFC
217CM
296MGOENCRUSTRATION/SPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK
0AMH08 0063
0MGOCONNECTION AT MH 9 O'CLOCK
185.1TFC
126RFJ
0MGOCONNECTION AT MH 3 O'CLOCK
297.8AMH08 0062
11.7CM
217FM
11.7FM
297.8CM

Properties (4)

additional_info
SC346771
custom_field_two
2
customer
LACSD
datetime