Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2018, 04:56 PM
  • E 0109_E 0108_9242018_100013.mp4

Date
09/24/2018
W/O
0730604
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00032
PipeID
P11336
Time
9:56 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7816
Sewer Name
E JOINT OUTFALL E - UNIT 5
City
LOS ANGELES
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
20180920DF_JOINT_OUTFALL_E_UNIT_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
E 0110
Downstream MH
E 0109
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
18
Pipe schematic from manhole E 0110 to E 0109
MH: E 0110MH: E 0109downstream0 ft. MWM - Water Mark, 100 %of cross sectional area0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:58 AM2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 25% MAG2 ft. MGP - General Photograph2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. MGO - General Observation - ROACHES2.1 ft. MSA - Survey Abandoned - HIGH WATER

Observation photos (8)

  • Water Mark, 100 %of cross sectional area

    0 ft. - Water Mark, 100 %of cross sectional area

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 25% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 25% MAG

  • General Photograph

    2 ft. - General Photograph

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - HIGH WATER

    2.1 ft. - Survey Abandoned - HIGH WATER

Observations (11)

DistanceCodeObservation
2SAP
0MWM
2SSS
2SZ25% MAG
0MWL
2MGP
2SRV
2SAV
2MGOROACHES
2.1MSAHIGH WATER
0AMH9:58 AM

Properties (4)

additional_info
VIEW OF DOWNLEG FROM THE U/S SIPHON
custom_field_two
5
customer
LACSD
datetime
2018-09-24T09:56:52-07:00