Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2017, 10:12 AM
  • 05 1095_05 1094_10032017_021235.mp4

Date
03/10/2017
W/O
624624
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00488
PipeID
P06329
Time
2:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4377
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
WO_624624_TV05328_MAR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
05 1095
Downstream MH
05 1094
Dir. of Survey
Downstream
Length Surveyed
325.1 ft.
Total Length
325.1 ft.
Structural Index
3
Structural Quick
3J23
Structural Rating
174
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
174
Pipe schematic from manhole 05 1095 to 05 1094
MH: 05 1095MH: 05 1094downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 10956 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES19.4 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES40.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES48.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"49.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start59.1 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES149 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"193.7 ft. FS - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES247.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"319 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish325.1 ft. AMH - Downstream Manhole, Survey Ends - 05 1094

Observation photos (6)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    6 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    19.4 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    40.7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    49.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

    59.1 ft. - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

    193.7 ft. - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
325.1AMH05 1094
19.4CL
319CM
0MWM
49.9CM
0MWL
59.1FC
6CL
0AMH05 1095
193.7FS
247.1TFC
40.7CM
48.2TFC
149TF

Properties (4)

additional_info
SC306886
custom_field_two
3
customer
LACSD
datetime
2017-03-10T02:12:25-08:00