Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2016, 07:27 AM
  • 15 0220_A 0576_11052016_002811.mp4

  • 15 0220_A 0576_11052016_040428.mp4

Date
05/11/2016
W/O
568733
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00627
PipeID
P12142
Time
12:27 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3346
Sewer Name
15 SAN JOSE CREEK TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Routine Assessment
Project
WO_568733_TV15133_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
15 0220
Downstream MH
A 0576
Dir. of Survey
Downstream
Length Surveyed
509.6 ft.
Total Length
509.6 ft.
Structural Index
3
Structural Quick
5B3f
Structural Rating
864
O&M Index
2
O&M Quick
2b00
O&M Rating
354
Overall Index
3
Overall Quick
Overall Rating
1218
Pipe schematic from manhole 15 0220 to A 0576
MH: 15 0220MH: A 0576downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 02200 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start90.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"134.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start138.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"238.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"334.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"382.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"425.8 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: YES432.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start443.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"509.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish509.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK509.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish509.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish509.6 ft. AMH - Downstream Manhole, Survey Ends - A 0576509.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish509.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish509.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

Observations (26)

DistanceCodeObservation
334.1TF
6.4SSS
90.1TFC
32.7SAP
509.6SAP
509.6MGOACTIVE CONNECTION AT MH 3 O'CLOCK
425.8SRV
286.7TBA
509.6SAV
382.8TFC
509.6DSZ
509.6AMHA 0576
509.6DAGS
432.6SRV
134.1DSZ
12.2SAV
0AMH15 0220
138.6TFC
443.2TFC
509.6SSS
0MGOCOCKROACHES IN MANHOLE
0MWM
238.2TFC
0MWL
2DAGS
509.6SRV

Properties (4)

additional_info
SC305625
custom_field_two
3
customer
LACSD
datetime
2016-05-11T00:27:43-07:00