Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 21, 2017, 11:12 AM
  • 18 0665_18 0664 _21112017_031317.mpg

Date
11/21/2017
W/O
668744
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14514
Time
3:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5042
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
WO_668744_TV18081_NOV2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0664
Downstream MH
18 0665
Dir. of Survey
Upstream
Length Surveyed
224.7 ft.
Total Length
224.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 0664 to 18 0665
MH: 18 0664MH: 18 0665upstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 12 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Ends - 18 06651.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish130.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"135.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"157.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start157.2 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish172.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start215.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.7 ft. AMH - Downstream Manhole, Survey Begins - 18 0664224.7 ft. MWM - Water Mark, 20 %of cross sectional area224.7 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (2)

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

    52 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    67.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
224.7MGOSERVICE CONNECTION AT 12 O' CLOCK AT MH
224.7AMH18 0665
94.5TFC
52CL
0AMH18 0664
89TF
0MWM
222.8CM
0MWL
9.2TFC
67.6CM
4.2TFC
67.5CL

Properties (4)

additional_info
SC346271
custom_field_two
3
customer
LACSD
datetime
2017-11-21T03:12:44-08:00