Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 24, 2016, 09:02 AM
  • 04 0080_04 0079_24022016_010320.mp4

Date
02/24/2016
W/O
552531
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11818
Time
1:02 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3265
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
WO_552531_TV04009_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
15 in.
Upstream MH
04 0079
Downstream MH
04 0080
Dir. of Survey
Upstream
Length Surveyed
356.1 ft.
Total Length
356.1 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
2]00
O&M Rating
296
Overall Index
2
Overall Quick
Overall Rating
506
Pipe schematic from manhole 04 0079 to 04 0080
MH: 04 0079MH: 04 0080upstream0 ft. AMH - Upstream Manhole, Survey Ends - 04 00802.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish2.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES34.3 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS37 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"62.1 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES75.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"77.7 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS114 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"124.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"128.4 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES157.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.6 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - FRACTURED212.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"214.9 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"234.4 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES255.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"263.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"275.6 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES299.6 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS301.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS342.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start348.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"350.7 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"351.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start354.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start356.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE356.1 ft. AMH - Downstream Manhole, Survey Begins - 04 0079356.1 ft. MWM - Water Mark, 20 %of cross sectional area356.1 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (14)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    13.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    54.2 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    56.5 ft. - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    80.5 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 12 o'clock,  , within 8 inches of joint: YES

    121.7 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - FRACTURED

    180.5 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - FRACTURED

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    227.7 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    278.4 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    294 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    321.8 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    350.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (32)

DistanceCodeObservation
5.4TBA
356.1AMH04 0080
7.9TFA
2DAGS
4.9CM
242.1TFA
92.7TFA
232TFA
354DAGS
141.2TFA
13.2DAE
121.7DAE
321.8TFDROOTS
354DAE
278.4TFDROOTS
54.2TFDROOTS
0MGOCOCKROACHES IN MANHOLE
354CM
0AMH04 0079
294DAE
80.5DAE
100.4TFA
0MWM
280.8TFA
144TFA
0MWL
56.5TFDROOTS
180.5TFDFRACTURED
319.1TFA
350.2DAE
198.3TFA
227.7DAE

Properties (4)

additional_info
SC225488