Section#1_J 0226_J 0225__12162017__G6884.mp4
2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR
2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG
8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
8 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - LONG REBAR
8.3 ft. - General Observation - 27" RCP
29.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR
31.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR
77 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG
109.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE
162.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORATIC
317.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE
| Distance | Code | Observation |
|---|---|---|
| 2 | SRC | LONG & CIRCUM REBAR |
| 0 | MWM | — |
| 29.2 | SRV | LONG & CIRCUM REBAR |
| 0 | MWL | — |
| 425.7 | AMH | 2:30AM |
| 17.7 | SRC | LONG & CIRCUM REBAR |
| 317.1 | SSS | PEELING CONCRETE |
| 425 | SAV | SEVERE AGG SPORATIC |
| 425 | SSS | BLISTERING PEELING CONCRETE |
| 77 | SAM | SEVERE AGG |
| 2 | SAM | SEVERE AGG |
| 8 | SRC | CIRCUM REBAR |
| 8 | SRV | LONG REBAR |
| 162.2 | SAM | SEVERE AGG |
| 0 | AMH | 1:45AM |
| 162.2 | SAV | SPORATIC |
| 425 | MGO | MH CONN 9:00 STUB |
| 109.3 | SSS | BLISTERING PEELING CONCRETE |
| 31.2 | SRV | CIRCUM REBAR |
| 63.1 | SRV | LONG & CIRCUM REBAR |
| 8.3 | MGO | 27" RCP |
| 425 | MGO | MH CONN 3:00 STUB |