- Date
- 12/23/2017
- W/O
- 0679364
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00062
- PipeID
- P11636
- Time
- 1:27 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0705
- Sewer Name
- J JOINT OUTFALL J - UNIT 2C
- City
- LOMITA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 32
- Purpose
- Capital Improvement Program Assesment
- Project
- 20171223MDM_JOINT_OUTFALL_J_UNIT_2C
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 42 in.
- Upstream MH
- J 0059
- Downstream MH
- J 0058
- Dir. of Survey
- Downstream
- Length Surveyed
- 687.9 ft.
- Total Length
- 687.9 ft.
- Structural Index
- 4
- Structural Quick
- 5141
- Structural Rating
- 12
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 12
Pipe schematic from manhole J 0059 to J 0058 Observation photos (7)

2 ft. - General Observation - MAG COAT 100% START 8:00 TO 4:00

33.3 ft. - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

301.2 ft. - General Observation - 100% MAG COAT

301.2 ft. - General Observation - 100% MAG COAT

349.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG UNDER MAG COAT

392 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

599.5 ft. - General Observation - 100% MAG COAT