Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 20, 2017, 11:18 AM
  • Section#7_J 0222_J 0219__12202017__G6888.mp4

Date
12/20/2017
W/O
0624519
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11467
Time
3:18 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6888
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47
Purpose
Capital Improvement Program Assesment
Project
20171216MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0222
Downstream MH
J 0219
Dir. of Survey
Downstream
Length Surveyed
1380.7 ft.
Total Length
1380.7 ft.
Structural Index
3
Structural Quick
5H4J
Structural Rating
1629
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
1629
Pipe schematic from manhole J 0222 to J 0219
MH: J 0222MH: J 0219downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM0 ft. MGO - General Observation - MH CONN OPEN 9:000 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE8.1 ft. MGO - General Observation - 27" RCP46.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE51.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC67.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Change - PEELING CONCRETE93.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG93.1 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR99.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR101.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR115.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR122.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG126.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR133.2 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR204.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR211.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR211.7 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR285.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR330 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - LONG & CIRCUM REBAR330 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC330 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC339.7 ft. SAM - Surface Aggregate Missing, from 08 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG339.7 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR345.7 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish357.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR357.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG410.3 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR410.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG430 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG430 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR544.5 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR1121.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELINJG CONCRETE1266.2 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR1272 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR1360.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR1367.6 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG1371.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR-MISSING1380.1 ft. MGO - General Observation - MH CONN 3:00 OPEN STOPLOG IN PLACE1380.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR1380.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG1380.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR1380.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE1380.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC1380.2 ft. MGO - General Observation - MH# J221 AREA AROUND AND BELOW MH LOOKS COMPROMISED1380.7 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (28)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - 27" RCP

    8.1 ft. - General Observation - 27" RCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    46.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC

    51.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Change - PEELING CONCRETE

    67.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Change - PEELING CONCRETE

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    93.1 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR

    93.1 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    99.8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    101.2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    122.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR

    126.8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    133.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    204.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR

    211.7 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    285.4 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC

    330 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC

  • Surface Aggregate Missing, from 08 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG

    339.7 ft. - Surface Aggregate Missing, from 08 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    339.7 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    357.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    410.3 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    410.3 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    544.5 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELINJG CONCRETE

    1121.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELINJG CONCRETE

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    1266.2 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    1360.8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    1367.6 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR-MISSING

    1371.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR-MISSING

  • General Observation - MH CONN 3:00 OPEN STOPLOG IN PLACE

    1380.1 ft. - General Observation - MH CONN 3:00 OPEN STOPLOG IN PLACE

Observations (48)

DistanceCodeObservation
115.5SRVLONG & CIRCUM REBAR
330SRVLONG & CIRCUM REBAR
8.1MGO27" RCP
2SSSBLISTERING PEELING CONCRETE
211.7SRVLONG & CIRCUM REBAR
1272SRVCIRCUM REBAR
330SAMSEVERE AGG SPORATIC
99.8SRVLONG & CIRCUM REBAR
67.1SSSPEELING CONCRETE
0MWL
285.4SRVCIRCUM REBAR
339.7SAMSEVERE AGG
357.3SRVCIRCUM REBAR
1380.1MGOMH CONN 3:00 OPEN STOPLOG IN PLACE
46.3SSSPEELING CONCRETE
93.1SAMSEVERE AGG
1380.1SRCCIRCUM REBAR
204.2SRVLONG & CIRCUM REBAR
410.3SRVCIRCUM REBAR
330SAVSEVERE AGG SPORATIC
1371.8SRCCIRCUM REBAR-MISSING
430SAMSEVERE AGG
1380.1SAMSEVERE AGG
345.7SRV
339.7SRVCIRCUM REBAR
1380.2MGOMH# J221 AREA AROUND AND BELOW MH LOOKS COMPROMISED
430SRVCIRCUM REBAR
1380.1SRVCIRCUM REBAR
1266.2SRVCIRCUM REBAR
126.8SRVLONG & CIRCUM REBAR
122.7SAVSEVERE AGG
0AMH3:30AM
1367.6SAMSEVERE AGG
1380.7AMH5:10AM
357.3SAMSEVERE AGG
211.7SRVLONG & CIRCUM REBAR
544.5SRVCIRCUM REBAR
0MGOMH CONN OPEN 9:00
1360.8SRVCIRCUM REBAR
101.2SRVLONG & CIRCUM REBAR
1121.2SSSBLISTERING PEELINJG CONCRETE
133.2SRVLONG REBAR
1380.1SSSBLISTERING PEELING CONCRETE
0MWM
410.3SAMSEVERE AGG
1380.1SAVSEVERE AGG SPORATIC
93.1SRVLONG & CIRCUM REBAR
51.2SAVSEVERE AGG VERY SPORATIC

Properties (4)

custom_field_three
LONG & CIRCUM REBAR VISIBLE,CORRODED & MISSING
custom_field_two
2
customer
LACSD
datetime
2017-12-20T03:18:34-08:00