Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2016, 11:26 AM
  • 05 1000_05 0999 _12302016_034154.mp4

Date
12/30/2016
W/O
613357
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00421
PipeID
P06232
Time
3:26 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3953
Sewer Name
05 AVIATION BOULEVARD TRUNK
City
EL SEGUNDO, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
WO_613357_TV05010_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0999
Downstream MH
05 1000
Dir. of Survey
Upstream
Length Surveyed
328.5 ft.
Total Length
328.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2P00
O&M Rating
170
Overall Index
2
Overall Quick
Overall Rating
170
Pipe schematic from manhole 05 0999 to 05 1000
MH: 05 0999MH: 05 1000upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 10001.4 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish53.6 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"88.8 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start128.5 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"206.5 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"279.4 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4", 4"322 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start328.5 ft. AMH - Upstream Manhole, Survey Begins - 05 0999328.5 ft. MWL - Water Level, 10 %of cross sectional area328.5 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Fine,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    239.7 ft. - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
122TBC
0AMH05 0999
49.1TBC
327.1DSF
6.5DAGS
239.7DSF
274.9TBC
200TBC
328.5AMH05 1000
327.1DAGS
0MWL
0MWM

Properties (4)

additional_info
SC306466
custom_field_two
4
customer
LACSD
datetime