Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 27, 2016, 09:51 AM
  • 05 1004_05 1003 _12272016_021346.mp4

Date
12/27/2016
W/O
613357
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00421
PipeID
P06236
Time
1:51 AM
Certificate
U507386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3949
Sewer Name
05 AVIATION BOULEVARD TRUNK
City
HAWTHORNE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
WO_613357_TV05010_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1004
Downstream MH
05 1003
Dir. of Survey
Downstream
Length Surveyed
198.1 ft.
Total Length
198.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2G00
O&M Rating
78
Overall Index
2
Overall Quick
Overall Rating
78
Pipe schematic from manhole 05 1004 to 05 1003
MH: 05 1004MH: 05 1003downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 10040 ft. MWM - Water Mark, 15 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"104.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"181.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"195.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish198.1 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE198.1 ft. AMH - Downstream Manhole, Survey Ends - 05 1003

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
181.3TFC
0MWL
198.1MGOCONNECTION AT MH 3 ACTIVE
0AMH05 1004
0MWM
198.1AMH05 1003
2.2DAGS
27.2TFC
104.3TFC
195.3DAGS

Properties (4)

additional_info
SC317697
custom_field_two
4
customer
LACSD
datetime
2016-12-27T01:51:16-08:00