Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2017, 07:58 AM
  • 02 1711_02 1710_01042017_235239.mp4

Date
01/04/2017
W/O
613349
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00289
PipeID
P18874
Time
11:58 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4050
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
06
Purpose
Routine Assessment
Project
WO_613349_TV02103_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1711
Downstream MH
02 1710
Dir. of Survey
Downstream
Length Surveyed
339 ft.
Total Length
339 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
134
Pipe schematic from manhole 02 1711 to 02 1710
MH: 02 1711MH: 02 1710downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 02 17110 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start75 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"133.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"215 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"248 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"278.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"308.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"311.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"326.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"337.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish337.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE339 ft. AMH - Downstream Manhole, Survey Ends - 02 1710

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    215 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - COCKROACHES IN MANHOLE

    337.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
133.9TFC
182.2TF
75TFC
0MWM
245.2TFA
0MGOCOCKROACHES IN MANHOLE
278.2TB
339AMH02 1710
337.2DAGS
248TFC
185.6TFC
2DAGS
337.2MGOCOCKROACHES IN MANHOLE
311.7TFC
112.2TBA
0AMH02 1711
0MWL
122.8TFC
326.1TBA
215TFA
308.4TFC

Properties (4)

additional_info
SC306448
custom_field_two
4
customer
LACSD
datetime
2017-01-04T23:58:58-08:00