Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2016, 07:38 AM
  • 03 0398_03 0397 _12272016_235237.mp4

Date
12/27/2016
W/O
613343
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00371
PipeID
P04973
Time
11:38 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3901
Sewer Name
03 MARINA TRUNK, SECTION 2
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
25
Purpose
Routine Assessment
Project
WO_613343_TV03019_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
03 0398
Downstream MH
03 0397
Dir. of Survey
Downstream
Length Surveyed
302 ft.
Total Length
302.1 ft.
Structural Index
1
Structural Quick
1300
Structural Rating
3
O&M Index
2
O&M Quick
2P11
O&M Rating
173
Overall Index
2
Overall Quick
Overall Rating
176
Pipe schematic from manhole 03 0398 to 03 0397
MH: 03 0398MH: 03 0397downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 03980 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK MADE2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start45.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"53 ft. VC - Vermin Cockroach, within 8 inches of joint: NO53.8 ft. CC - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES95.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"104.1 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES109.1 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES154.8 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 08 o'clock, Start - DEBRIS NOT VISIBLE195.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"251.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"292.3 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 08 o'clock, Finish - DEBRIS NOT VISIBLE297.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish302.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE302.1 ft. AMH - Downstream Manhole, Survey Ends - 03 0397302.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK MADE

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

    53.8 ft. - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

    104.1 ft. - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    109.1 ft. - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
302.1MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
0MWL
302.1AMH03 0397
251.7TFC
297.8DAGS
109.1CC
0AMH03 0398
195.8TFC
53VC
2.2DAGS
292.3OBZDEBRIS NOT VISIBLE
154.8OBZDEBRIS NOT VISIBLE
0MWM
95.6TFC
104.1CC
0MGOCONNECTION AT MH 3 O'CLOCK MADE
53.8CC
302.1MGOCONNECTION AT MH 9 O'CLOCK MADE
45.8TFC

Properties (4)

additional_info
SC305242
custom_field_two
4
customer
LACSD
datetime
2016-12-27T23:38:23-08:00