Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2016, 03:36 PM
  • 22 0913_22 0912 _01112016_084825.mp4

Date
11/01/2016
W/O
591687
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00799
PipeID
P17284
Time
8:36 AM
Certificate
12345
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3957
Sewer Name
22 CONEY TRUNK, SECTS 2&3
City
AZUSA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
WO_591687_TV22133_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0913
Downstream MH
22 0912
Dir. of Survey
Downstream
Length Surveyed
231.2 ft.
Total Length
231.2 ft.
Structural Index
5
Structural Quick
5G00
Structural Rating
210
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
214
Pipe schematic from manhole 22 0913 to 22 0912
MH: 22 0913MH: 22 0912downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 6 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 091341.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"81.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"184.6 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"192.7 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"231.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0912231.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK

Observations (10)

DistanceCodeObservation
41.5TB
81.6TBA
231.2AMH22 0912
0MWL
0MGOCONNECTION AT THE MH 6 O'CLOCK
184.6TBC
0MWM
231.2MGOCONNECTION AT THE MH 9 O'CLOCK
192.7TBC
0AMH22 0913

Properties (4)

additional_info
SC303677
custom_field_two
4
customer
LACSD
datetime
2016-11-01T08:36:29-07:00