Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2017, 08:21 AM
  • 05 1811_05 1810 _17022017_002110.mpg

Date
02/17/2017
W/O
618877
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00466
PipeID
P07034
Time
12:21 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4155
Sewer Name
05 JANET LANE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Routine Assessment
Project
WO_618877_TV05053_FEB2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 1811
Downstream MH
05 1810
Dir. of Survey
Downstream
Length Surveyed
350.4 ft.
Total Length
350.4 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
1
O&M Quick
1400
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
211
Pipe schematic from manhole 05 1811 to 05 1810
MH: 05 1811MH: 05 1810downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18116.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.7 ft. RFJ - Roots Fine Joint, from 08 to 02 o'clock, within 8 inches of joint: YES48.4 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YES191.7 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES222 ft. RFJ - Roots Fine Joint, from 10 to 12 o'clock, within 8 inches of joint: YES350.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1810350.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YES

    48.4 ft. - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
222RFJ
0MWL
48.4RFJ
6.1CM
350.4AMH05 1810
350.4CM
0MWM
0AMH05 1811
9.7RFJ
191.7RFJ

Properties (4)

additional_info
SC306861
custom_field_two
3
customer
LACSD
datetime
2017-02-17T00:21:02-08:00