Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 6, 2017, 07:00 AM
  • A 0709_A 0708 _08122017_143006.mp4

Date
12/05/2017
W/O
674024
Weather
Dry
Operator/Surveyor
ERUIZ
Sewer ID
Z00316
PipeID
P07918
Time
11:00 PM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5152
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
POMONA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
14
Purpose
Routine Assessment
Project
WO_674024_TV21041_DEC2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
A 0709
Downstream MH
A 0708
Dir. of Survey
Downstream
Length Surveyed
295.4 ft.
Total Length
295.4 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole A 0709 to A 0708
MH: A 0709MH: A 0708downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 07090.1 ft. MWM - Water Mark, 25 %of cross sectional area8 ft. MGO - General Observation - MAGNESIUM COATING START21.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start69.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"191.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish235.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start290.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish295.4 ft. AMH - Downstream Manhole, Survey Ends - A 0708

Observation photos (2)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    21.5 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    235.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
290.6SAP
0MWL
0AMHA 0709
69.5TFA
235.6SAP
0.1MWM
191.1SRV
8MGOMAGNESIUM COATING START
21.5SRV
295.4AMHA 0708

Properties (5)

additional_info
SC346462
custom_field_two
2
customer
LACSD
datetime
2017-12-05T23:00:52-08:00
year_laid
26232