Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2017, 11:59 AM
  • 02 1304_02 1303_28112017_035946.mp4

Date
11/28/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03823
Time
3:59 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5052
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1304
Downstream MH
02 1303
Dir. of Survey
Downstream
Length Surveyed
325.1 ft.
Total Length
325.1 ft.
Structural Index
3
Structural Quick
3K21
Structural Rating
185
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
186
Pipe schematic from manhole 02 1304 to 02 1303
MH: 02 1304MH: 02 1303downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13040 ft. MWL - Water Level, 5 %of cross sectional area12.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"16.6 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES18.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.3 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"58.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"105.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"164 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"218.1 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES219.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"258.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"276.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"325.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1303

Observation photos (2)

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    16.6 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
218.1RFJ
325.1CM
276.3TF
164TF
58.7TF
258.6TF
16.6CL
23.3TB
0MWM
12.8TFC
105.1TF
219.3TFA
325.1AMH02 1303
18.6CM
0AMH02 1304
0MWL

Properties (4)

additional_info
SC346281
custom_field_two
3
customer
LACSD
datetime
2017-11-28T03:59:11-08:00