Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2018, 09:54 AM
  • 29 0201_29 0180 _29012018_020858.mp4

Date
01/29/2018
W/O
684976
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01025
PipeID
P24100
Time
1:54 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5425
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
WO_684976_TV29048_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0201
Downstream MH
29 0180
Dir. of Survey
Downstream
Length Surveyed
336 ft.
Total Length
336 ft.
Structural Index
3
Structural Quick
4134
Structural Rating
19
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 29 0201 to 29 0180
MH: 29 0201MH: 29 0180downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02010 ft. MWM - Water Mark, 5 %of cross sectional area7.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"9.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"55.9 ft. TF - Defective Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Fracture / Hole @ Lateral / Pipe56.9 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES74.1 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES106.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES108.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"156.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.8 ft. TS - Tap Factory Made Defective Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Gap where pipe (conn.) meets wall - possible soil present.206.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES253.9 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES258.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"261 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.5 ft. CM - Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES307.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"310.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.7 ft. FM - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES336 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK336 ft. AMH - Downstream Manhole, Survey Ends - 29 0180

Observation photos (8)

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    56.9 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

    74.1 ft. - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    107.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Gap where pipe (conn.) meets wall - possible soil present.

    158.8 ft. - Tap Factory Made Defective Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Gap where pipe (conn.) meets wall - possible soil present.

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    226.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    253.9 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

    265.5 ft. - Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

    331.7 ft. - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
106.1TFC
206.3TFC
158.8TSGap where pipe (conn.) meets wall - possible soil present.
107.4CM
0MWL
253.9CM
7.2TFC
307.7TFC
310.2TFC
261TFC
74.1CC
9.4TFA
56.9CM
0AMH29 0201
55.9TFFracture / Hole @ Lateral / Pipe
156.2TFC
258.3TFC
0MWM
331.7FM
108.4TFC
208.3TFC
336MGOCONNECTION AT MH 9 O'CLOCK
226.9CL
53.3TFC
265.5CM
336AMH29 0180

Properties (4)

additional_info
SC347060
custom_field_two
1
customer
LACSD
datetime