Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2018, 09:35 AM
  • 29 0202_29 0201 _29012018_015341.mp4

Date
01/29/2018
W/O
684976
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01025
PipeID
P24101
Time
1:35 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5425
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
WO_684976_TV29048_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0202
Downstream MH
29 0201
Dir. of Survey
Downstream
Length Surveyed
311.8 ft.
Total Length
311.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 29 0202 to 29 0201
MH: 29 0202MH: 29 0201downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02020 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK66.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"116 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"169.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.7 ft. TF - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - FRACTURES @ & LEADING TO LATERAL -BROKEN LATERAL-219 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"266 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"304 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES311.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0201

Observation photos (1)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    304 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
66.7TFC
311.8AMH29 0201
216.7TFFRACTURES @ & LEADING TO LATERAL -BROKEN LATERAL-
169.5TFC
266TFC
116TFC
268.4TFC
117.9TFC
304CM
0MWL
219TF
167.1TFC
0AMH29 0202
69.6TF
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (4)

additional_info
SC347060
custom_field_two
1
customer
LACSD
datetime
2018-01-29T01:35:34-08:00