Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 8, 2018, 12:20 PM
  • Section#7_18 0857_18 0856__582018__I0002.mp4

Date
05/08/2018
W/O
0701110
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00709
PipeID
P14712
Time
5:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0002
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Routine Assessment
Project
20180504MDM_SO_WHITTIER_OUTFALL_RLF_TR_SECTS_1_2A_2B_2C_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
18 0857
Downstream MH
18 0856
Dir. of Survey
Downstream
Length Surveyed
70.9 ft.
Total Length
70.9 ft.
Structural Index
3
Structural Quick
5242
Structural Rating
61
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
61
Pipe schematic from manhole 18 0857 to 18 0856
MH: 18 0857MH: 18 0856downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:25AM0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG8.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG8.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR8.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG70.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE70.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG70.9 ft. AMH - Downstream Manhole, Survey Ends - 5:35AM

Observation photos (4)

  • Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2.1 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    8.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

Observations (12)

DistanceCodeObservation
70.7SSSBLISTERING PEELING CONCRETE
0AMH5:25AM
2SRCCIRCUM REBAR
70.7SAVSEVERE AGG
8.1SAVSEVERE AGG
70.9AMH5:35AM
2.1SAMSEVERE AGG
0MWL
8.1SRCCIRCUM REBAR
2SSSBLISTERING PEELING CONCRETE
8.1SAMSEVERE AGG
0MWM

Properties (4)

custom_field_three
CORRODED CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2018-05-08T05:20:00-07:00