Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2018, 01:13 PM
  • Section#4_18 0861_18 0858__552018__G6999.mp4

Date
05/05/2018
W/O
0701110
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00709
PipeID
P20535
Time
6:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6999
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Capital Improvement Program Assesment
Project
20180504MDM_SO_WHITTIER_OUTFALL_RLF_TR_SECTS_1_2A_2B_2C_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
18 0861
Downstream MH
18 0858
Dir. of Survey
Downstream
Length Surveyed
716.9 ft.
Total Length
716.9 ft.
Structural Index
3
Structural Quick
3F23
Structural Rating
117
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
117
Pipe schematic from manhole 18 0861 to 18 0858
MH: 18 0861MH: 18 0858downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 6:30AM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Change - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 80% START 9:00 TO 3:0025.9 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC32.4 ft. SAV - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG136.8 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG204.6 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AG211.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE237.1 ft. SAV - Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG268.3 ft. SAV - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC401.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE454.4 ft. SAV - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG458 ft. SAP - Surface Aggregate Projecting, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG551.7 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG577.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC716.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC716.3 ft. MGO - General Observation - MAG COAT 80% FINISH716.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE716.3 ft. MGO - General Observation - MH CONN 3:00 ACTIVE716.9 ft. AMH - Downstream Manhole, Survey Ends - 7:30AM

Observation photos (12)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Change - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Change - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 80% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 80% START 9:00 TO 3:00

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    25.9 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

    32.4 ft. - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    136.8 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

    211.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    237.1 ft. - Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

    268.3 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

    454.4 ft. - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Projecting, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    458 ft. - Surface Aggregate Projecting, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    551.7 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    577.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

Observations (22)

DistanceCodeObservation
204.6SAVSEVERE AG
454.4SAVSEVERE AGG
716.3SAVSEVERE AGG SPORATIC
2SSSBLISTERING PEELING CONCRETE
577.8SAVSEVERE AGG SPORATIC
716.9AMH7:30AM
32.4SAVSEVERE AGG
551.7SAVSEVERE AGG
716.3MGOMAG COAT 80% FINISH
25.9SAVSEVERE AGG SPORATIC
716.3SSSBLISTERING PEELING CONCRETE
458SAPSEVERE AGG
716.3MGOMH CONN 3:00 ACTIVE
2MGOMAG COAT 80% START 9:00 TO 3:00
0MWM
237.1SAVSEVERE AGG
268.3SAVSEVERE AGG SPORATIC
0AMH6:30AM
401.5TFACTIVE
136.8SAVSEVERE AGG
211.1SSSBLISTERING PEELING CONCRETE
0MWL

Properties (4)

custom_field_three
VISIBLE & PROJECTING SEVERE AGG
custom_field_two
3
customer
LACSD
datetime
2018-05-05T06:13:00-07:00