Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2017, 06:27 AM
  • F 0077_F 0254 _09052017_233051.mp4

Date
05/09/2017
W/O
630328
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00036
PipeID
P10178
Time
11:27 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4449
Sewer Name
F JOINT OUTFALL F - UNIT 3A RELIEF
City
CERRITOS
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_630328_TV02208_APR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
66 in.
Width
66 in.
Upstream MH
F 0254
Downstream MH
F 0077
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole F 0254 to F 0077
MH: F 0254MH: F 0077upstream0 ft. AMH - Upstream Manhole, Survey Ends - F 00770 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES0 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES2 ft. AMH - Downstream Manhole, Survey Begins - F 02542 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES

Observations (5)

DistanceCodeObservation
2AMHF 0077
2SAP
2SRV
0AMHF 0254
0MWL

Properties (5)

additional_info
SC345224
custom_field_two
2
customer
LACSD
datetime
2017-05-09T23:27:17-07:00
year_laid
27333