Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 6, 2016, 09:15 AM
  • 01 0171_01 0170B_06092016_021605.mp4

Date
09/06/2016
W/O
585995
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01200
Time
2:15 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3579
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_585995_TV01012_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0171
Downstream MH
01 0170B
Dir. of Survey
Downstream
Length Surveyed
30.4 ft.
Total Length
30.4 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 0171 to 01 0170B
MH: 01 0171MH: 01 0170Bdownstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 01710 ft. MWL - Water Level, 5 %of cross sectional area5.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start14.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES15.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"30.4 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK30.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0170B30.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    5.9 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    14.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
30.4MGOLATERAL AT MH 3 OCLOCK
30.4AMH01 0170B
30.4DSZ
0MGOLATERAL AT MH 9 OCLOCK
0MWM
15.2TFC
0AMH01 0171
5.9DSZ
0MWL
14.8CL

Properties (4)

additional_info
SC306169
custom_field_two
4
customer
LACSD
datetime
2016-09-06T02:15:48-07:00