Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2016, 11:29 AM
  • 01 0200_01 0199_29082016_042946.mp4

Date
08/29/2016
W/O
585995
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01242
Time
4:29 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3574
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_585995_TV01012_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0200
Downstream MH
01 0199
Dir. of Survey
Downstream
Length Surveyed
304.9 ft.
Total Length
304.9 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
177
Pipe schematic from manhole 01 0200 to 01 0199
MH: 01 0200MH: 01 0199downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02000 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK4.2 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES10.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start12.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"44.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"70.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"123.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"150.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"217.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"282.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"302.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish302.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"304.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0199

Observation photos (2)

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    4.2 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
187.6TFA
4.2CM
0AMH01 0200
150.2TF
70.9TF
185.7TFC
123.8TF
0MWM
12.4TF
0MWL
100.4TF
282.3TF
246.6TF
302.5CM
10.3CM
0MGOLATERAL AT MH 9 OCLOCK
44.8TF
302.5TF
304.9AMH01 0199
217.4TFC
232TF

Properties (4)

additional_info
SC306162
custom_field_two
3
customer
LACSD
datetime