Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 7, 2016, 08:31 AM
  • 01 1009_01 1008_07092016_013208.mp4

Date
09/07/2016
W/O
585982
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00221
PipeID
P01855
Time
1:31 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3580
Sewer Name
01 VERNON EXTENSION TRUNK
City
VERNON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_585982_TV01065_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 1009
Downstream MH
01 1008
Dir. of Survey
Downstream
Length Surveyed
330.8 ft.
Total Length
330.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
118
Pipe schematic from manhole 01 1009 to 01 1008
MH: 01 1009MH: 01 1008downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 10090 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 6 OCLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK25.6 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES41.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start161.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"163.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"217.7 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES261.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"263.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish330.8 ft. AMH - Downstream Manhole, Survey Ends - 01 1008

Observation photos (3)

  • Deposits Settled Other,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES

    25.6 ft. - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    41.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES

    217.7 ft. - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
0AMH01 1009
261.8TFC
25.6DSZ
0MWM
217.7DSZ
0MGOLATERAL AT MH 6 OCLOCK
163.8TFC
0MWL
325.2DAGS
263.7TFC
41.3DAGS
330.8AMH01 1008
0MGOLATERAL AT MH 9 OCLOCK
161.5TFC

Properties (4)

additional_info
SC306170
custom_field_two
4
customer
LACSD
datetime