- Date
- 09/07/2016
- W/O
- 585982
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00221
- PipeID
- P01842
- Time
- 3:38 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K3580
- Sewer Name
- 01 VERNON EXTENSION TRUNK
- City
- HUNTINGTON PARK
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 04
- Purpose
- Routine Assessment
- Project
- WO_585982_TV01065_AUG2016
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- 01 1001
- Downstream MH
- 01 1000
- Dir. of Survey
- Downstream
- Length Surveyed
- 284.5 ft.
- Total Length
- 284.6 ft.
- Structural Index
- 3
- Structural Quick
- 3400
- Structural Rating
- 12
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 12
Pipe schematic from manhole 01 1001 to 01 1000 Observation photos (4)

14.4 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

22.8 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

110.5 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

155.6 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES