Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2016, 05:32 AM
  • 01 0997_01 0996_12092016_223235.mp4

Date
09/12/2016
W/O
585982
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00221
PipeID
P01838
Time
10:32 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3581
Sewer Name
01 VERNON EXTENSION TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_585982_TV01065_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0997
Downstream MH
01 0996
Dir. of Survey
Downstream
Length Surveyed
385.1 ft.
Total Length
385.2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0997 to 01 0996
MH: 01 0997MH: 01 0996downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 09970 ft. MWM - Water Mark, 20 %of cross sectional area34.2 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES368 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES385.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0996

Observation photos (2)

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    34.2 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    368 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
385.2AMH01 0996
0MWL
0AMH01 0997
368CL
0MWM
34.2CM

Properties (4)

additional_info
SC306174