Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2016, 06:45 AM
  • 01 0993_01 0992_12092016_234550.mp4

Date
09/12/2016
W/O
585982
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00221
PipeID
P01833
Time
11:45 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3581
Sewer Name
01 VERNON EXTENSION TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_585982_TV01065_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0993
Downstream MH
01 0992
Dir. of Survey
Downstream
Length Surveyed
340.8 ft.
Total Length
340.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2G00
O&M Rating
76
Overall Index
2
Overall Quick
Overall Rating
76
Pipe schematic from manhole 01 0993 to 01 0992
MH: 01 0993MH: 01 0992downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 09930 ft. MWM - Water Mark, 20 %of cross sectional area41.9 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start161.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"232.9 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish340.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0992

Observation photos (3)

  • Deposits Settled Other,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    41.9 ft. - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    161.4 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    231.5 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

Observations (8)

DistanceCodeObservation
41.9DSZ
0MWL
161.4TB
0AMH01 0993
0MWM
232.9DSZ
231.5TB
340.8AMH01 0992

Properties (4)

additional_info
SC306174
custom_field_two
4
customer
LACSD
datetime
2016-09-12T23:45:43-07:00