Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2018, 07:53 AM
  • 01 1198_01 1155_13082018_010649.mp4

Date
08/13/2018
W/O
717681
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00226
PipeID
P02108
Time
12:53 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5981
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
WO_717681_TV01250_AUG2018
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
01 1198
Downstream MH
01 1155
Dir. of Survey
Downstream
Length Surveyed
85.5 ft.
Total Length
85.5 ft.
Structural Index
3
Structural Quick
3B21
Structural Rating
44
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
44
Pipe schematic from manhole 01 1198 to 01 1155
MH: 01 1198MH: 01 1155downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11988.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES11.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish68.4 ft. SCP - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start68.4 ft. MMC - Material Change, Cast Iron85.4 ft. MMC - Material Change, Vitrified clay pipe85.4 ft. SCP - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish85.5 ft. AMH - Downstream Manhole, Survey Ends - 01 115585.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    8.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    68.4 ft. - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Material Change, Cast Iron

    68.4 ft. - Material Change, Cast Iron

  • Material Change, Vitrified clay pipe

    85.4 ft. - Material Change, Vitrified clay pipe

Observations (13)

DistanceCodeObservation
68.4CM
68.4SCP
0MWM
8.7CL
85.4MMC
35.3TFC
85.4SCP
68.4MMC
0MWL
11.5CM
85.5AMH01 1155
85.5MGOCONNECTION AT MH 3 O'CLOCK
0AMH01 1198

Properties (4)

additional_info
SC364745
custom_field_two
3
customer
LACSD
datetime