Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2017, 04:58 AM
  • C 0102A_C 0102 _20092017_224330.mp4

Date
09/20/2017
W/O
657771
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00123
PipeID
P09570
Time
9:58 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4884
Sewer Name
C JOINT OUTFALL C - UNIT 3D
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Routine Assessment
Project
WO_657771_TV03156_SEP2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
51 in.
Upstream MH
C 0102A
Downstream MH
C 0102
Dir. of Survey
Downstream
Length Surveyed
249 ft.
Total Length
249 ft.
Structural Index
4
Structural Quick
5H3I
Structural Rating
367
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
371
Pipe schematic from manhole C 0102A to C 0102
MH: C 0102AMH: C 0102downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 0102A0 ft. MWL - Water Level, 60 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 70 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.3 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start248.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish248.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish249 ft. MSA - Survey Abandoned - HIGH FLOW CAM HITTING TOP OF PIPE

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    28.3 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMHC 0102A
28.3SRV
248.6SAP
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
249MSAHIGH FLOW CAM HITTING TOP OF PIPE
248.6SRV
2.1SAP
0MWM

Properties (4)

additional_info
SC345944
custom_field_two
2
customer
LACSD
datetime
2017-09-20T21:58:26-07:00