Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2018, 07:21 AM
  • 22 0958_22 0957_16082018_004135.mp4

Date
08/16/2018
W/O
717737
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00790
PipeID
P17328
Time
12:21 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5902
Sewer Name
22 BASE LINE TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
WO_717737_TV22002_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0958
Downstream MH
22 0957
Dir. of Survey
Downstream
Length Surveyed
442.3 ft.
Total Length
442.3 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
264
O&M Index
2
O&M Quick
2Q00
O&M Rating
178
Overall Index
3
Overall Quick
Overall Rating
442
Pipe schematic from manhole 22 0958 to 22 0957
MH: 22 0958MH: 22 0957downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 09582 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"92.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES188.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"237.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"241.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"326.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"338.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"441.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish441.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish441.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE442.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK442.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0957

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 10 o'clock,  , within 8 inches of joint: YES

    163.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
92.4TFC
0MWM
441.4DAGS
39.7TFC
188.6TFC
441.4SAV
2DAGS
442.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
326.9TBA
338.4TFC
100.6TFC
0MWL
442.3AMH22 0957
2SAV
241.3TFC
163.8DAGS
0AMH22 0958
441.4MGOCOCKROACHES IN MANHOLE
289.8TFC
237.4TFC

Properties (4)

additional_info
SC364772
custom_field_two
3
customer
LACSD
datetime