Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 12, 2018, 04:15 PM
  • D 0073_D 0072_9122018_095103.mp4

Date
09/12/2018
W/O
0726352
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00154
PipeID
P09973
Time
9:15 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7807
Sewer Name
D JOINT OUTFALL D - UNIT 4
City
HAWTHORNE
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20180906DF_JOINT_OUTFALL_D_UNIT_4
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
D 0073
Downstream MH
D 0072
Dir. of Survey
Downstream
Length Surveyed
162.8 ft.
Total Length
162.8 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole D 0073 to D 0072
MH: D 0073MH: D 0072downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:22 AM2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 05 o'clock, , within 8 inches of joint: YES43.2 ft. MGP - General Photograph43.2 ft. MGP - General Photograph52.8 ft. MGP - General Photograph100 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start101.6 ft. MGP - General Photograph134.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"142.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"159.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish159.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish159.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish159.5 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish159.5 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 55% MAG159.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish162.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active162.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active162.8 ft. AMH - Downstream Manhole, Survey Ends - 10:15 AM162.8 ft. MGO - General Observation - Grease Throughout The Reach (5%)162.8 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach

Observation photos (11)

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 05 o'clock,  , within 8 inches of joint: YES

    33 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 05 o'clock, , within 8 inches of joint: YES

  • General Photograph

    43.2 ft. - General Photograph

  • General Photograph

    43.2 ft. - General Photograph

  • General Photograph

    52.8 ft. - General Photograph

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    100 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    101.6 ft. - General Photograph

  • General Observation - Conn. @ Mh, 9 O' Clock. Active

    162.5 ft. - General Observation - Conn. @ Mh, 9 O' Clock. Active

Observations (27)

DistanceCodeObservation
159.5SRV
0MWM
159.5SAP
43.2MGP
43.2MGP
159.5SSS
0MWL
162.8AMH10:15 AM
2SZ55% MAG
101.6MGP
162.8MGOGrease Throughout The Reach (5%)
2SRV
0AMH9:22 AM
52.8MGP
2SAP
100SRC
33DAGS
2SSS
162.8MGOPeeling & Flaking Throughout The Reach
2SAV
162.5MGOConn. @ Mh, 3 O' Clock. Active
159.5SRC
162.5MGOConn. @ Mh, 9 O' Clock. Active
142.6TFC
159.5SZ55% MAG
159.5SAV
134.3TFC

Properties (3)

custom_field_two
2
customer
LACSD
datetime
2018-09-12T09:15:26-07:00