Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2017, 06:37 AM
  • 01 0086_01 0085_01052017_234114.mp4

Date
05/01/2017
W/O
630384
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00755
Time
11:37 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4440
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_630384_TV01254_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0086
Downstream MH
01 0085
Dir. of Survey
Downstream
Length Surveyed
353.8 ft.
Total Length
353.8 ft.
Structural Index
4
Structural Quick
4M00
Structural Rating
280
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
3
Overall Quick
Overall Rating
424
Pipe schematic from manhole 01 0086 to 01 0085
MH: 01 0086MH: 01 0085downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00862 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start67.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"123 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"174.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"218.7 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"222 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"245.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"275.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"352.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK352.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish352.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish353.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0085353.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (2)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
353.8AMH01 0085
2FM
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
215.4TFC
325.2TBA
0MWM
298.4TBC
222TB
123TFA
174.2TFA
275.7TFA
245.5TFC
353.8MGOCOCKROACHES IN MANHOLE
0MWL
218.7TBC
67.5TFC
352.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMH01 0086
2DAGS
352.3DAGS
352.3FM

Properties (4)

additional_info
SC345212
custom_field_two
3
customer
LACSD
datetime
2017-05-01T23:37:28-07:00