Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2017, 09:27 AM
  • B 1015_15 0725 _08062017_034355.mp4

Date
06/08/2017
W/O
640598
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00616
PipeID
P12619
Time
2:27 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4544
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_640598_TV15132_JUN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
B 1015
Downstream MH
15 0725
Dir. of Survey
Downstream
Length Surveyed
72.6 ft.
Total Length
72.6 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
42
O&M Index
2
O&M Quick
2B11
O&M Rating
29
Overall Index
2
Overall Quick
Overall Rating
71
Pipe schematic from manhole B 1015 to 15 0725
MH: B 1015MH: 15 0725downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT 9 OC0 ft. AMH - Upstream Manhole, Survey Begins - B 10152.5 ft. MGO - General Observation - MAG COATING2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. VC - Vermin Cockroach72.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish72.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish72.6 ft. MGO - General Observation - CONNECTION AT 9 OC72.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0725

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
72.6MGOCONNECTION AT 9 OC
0MWL
2.5MGOMAG COATING
0MWM
2.5DAGS
72.6AMH15 0725
2.5SAP
0MGOCONNECTION AT 9 OC
72.4SAP
72.4DAGS
0AMHB 1015
2.5VC

Properties (4)

additional_info
SC345359
custom_field_two
3
customer
LACSD
datetime
2017-06-08T02:27:46-07:00