Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2017, 05:11 AM
  • 15 0356_15 0355 _13042017_221257.mp4

Date
04/13/2017
W/O
630214
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00598
PipeID
P12282
Time
10:11 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4465
Sewer Name
15 BALDWIN PARK TRUNK
City
BALDWIN PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_630214_TV15016_APR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0356
Downstream MH
15 0355
Dir. of Survey
Downstream
Length Surveyed
347.8 ft.
Total Length
347.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0356 to 15 0355
MH: 15 0356MH: 15 0355downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 03560 ft. MWM - Water Mark, 30 %of cross sectional area2.2 ft. MGO - General Observation - mag coat2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"50 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"78.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"135 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"178.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"182.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"214.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"238.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"274.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"279 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"327.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"347.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish347.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0355

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
30.1TFC
178.5TFC
214.9TF
182.4TFC
0MWL
347.8SAV
347.8AMH15 0355
0AMH15 0356
50TFC
274.9TFC
106.2TF
279TF
2.2MGOmag coat
130.5TFC
2.2SAV
135TF
78.8TFC
238.9TF
0MWM
327.4TF

Properties (4)

additional_info
SC345174
custom_field_two
3
customer
LACSD
datetime
2017-04-13T22:11:48-07:00