Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2016, 10:35 AM
  • 22 0487_22 0486_20160421_045711.mp4

Date
04/21/2016
W/O
563425
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00800
PipeID
P16826
Time
3:35 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3187
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_563425_TV22031_APRIL2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
22 0486
Downstream MH
22 0487
Dir. of Survey
Upstream
Length Surveyed
329.6 ft.
Total Length
329.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 22 0486 to 22 0487
MH: 22 0486MH: 22 0487upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 04872.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish33 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"35.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"83.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"86.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"121.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"125.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"175.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"178.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"223.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"226.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"274.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"277.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"312.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"316.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"327.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start329.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK329.6 ft. MWL - Water Level, 15 %of cross sectional area329.6 ft. AMH - Downstream Manhole, Survey Begins - 22 0486329.6 ft. MWM - Water Mark, 30 %of cross sectional area329.6 ft. VC - Vermin Cockroach

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 9 OC'LOCK
204.5TFC
0MWL
208TF
153.9TF
327.5SAV
0AMH22 0486
294TFC
151.1TFC
52.3TFC
296.6TF
103.3TFC
17.2TFC
245.8TFC
329.6AMH22 0487
0MWM
243.2TFC
55.3TFC
0VC
2SAV
13.2TFC
106TF

Properties (4)

additional_info
SC226235
custom_field_two
3
customer
LACSD
datetime
2016-04-21T03:35:50-07:00